Still deciding? Get samples of $ !
Request Sample
|
| Customization: | Available |
|---|---|
| Energy Efficiency Grade: | Two |
| Heat Temperature: | 50-60 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency


| Model | WHP-100HC - 33KW | WHP-120HC - 40KW |
| Power Supply - Refrigerant | 380-415V/3PH/50HZ - R410A | |
| Heating Capacity ( KW ) - A | 33 | 40 |
| Rated Input Power ( KW ) - A | 9.1 | 11.1 |
| COP ( W/W ) - A | 3.63 | 3.60 |
| Heating Capacity ( KW ) - B | 22 | 27 |
| Rated Input Power ( KW ) - B | 8.65 | 10.5 |
| COP ( W/W ) - B | 2.54 | 2.57 |
| Cooling Capacity ( KW ) - C | 23 | 30 |
| Rated Input Power ( KW ) - C | 8 | 11.3 |
| EER ( W/W ) - C | 2.88 | 2.65 |
| Max. Input Power ( KW ) | 13 | 16 |
| Max. Input Current ( A ) | 20 | 25 |
| Compressor | Hitachi Scroll - EVI Technology | |
| Fan Type | High Efficiency Axial Flow Fan | |
| Fan Quantity ( Pcs ) | 1 | 1 |
| Fan Airflow ( m3/h ) | 14000 | 14000 |
| Fan Rated Power ( W ) | 750 | 750 |
| Heat exchanger | High Efficient Tank& Coil Type Heat Exchanger | |
| WaterSide Pressure Drop ( Kpa ) | 84 | 84 |
| Inlet/Outlet Pipe Size ( mm ) | DN40 | DN40 |
| Min. Flow ( m3/H ) | >6.2 | >7.8 |
| Noise ( dB(A) ) | ≤63 | ≤65 |
| Heating Water Temp. ºC | 20 ~ 60ºC | |
| Cooling Water Temp. ºC | 5 ~ 20 ºC | |
| Operating Ambient Temp. ºC | -35°C~45ºC | |
| Unit Dimension ( mm ) | 970*1000*1900 | 970*1000*1900 |
| Weight ( KG ) | 260kg/300kg | 280kg/310kg |
| Performance Condition - A : Ambient temp. (DB/WB): 7°C/6°C, Water temp. (In/Out): 40°C/ 45°C; | ||
| Performance Condition - B : Ambient temp. (DB/WB): -12°C/-14°C, Water temp. (Out): 41°C | ||
| Performance Condition - C: Ambient temp. (DB/WB): 35°C/24°C, Water temp. (In/Out): 12°C/7°C. | ||