Still deciding? Get samples of $ !
Request Sample
|
| Customization: | Available |
|---|---|
| Energy Efficiency Grade: | Two |
| Heat Temperature: | 50-60 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency


| Model | WHP-200HC- 66 KW | WHP-250HC - 80KW |
| Power Supply - Refrigerant | 380-415V/3PH/50HZ - R410A | |
| Heating Capacity ( KW ) - A | 66 | 80 |
| Rated Input Power ( KW ) - A | 18.1 | 22 |
| COP ( W/W ) - A | 3.65 | 3.64 |
| Heating Capacity ( KW ) - B | 44 | 54 |
| Rated Input Power ( KW ) - B | 17.3 | 21.2 |
| COP ( W/W ) - B | 2.54 | 2.55 |
| Cooling Capacity ( KW ) - C | 46 | 60 |
| Rated Input Power ( KW ) - C | 16 | 22.8 |
| EER ( W/W ) - C | 2.88 | 2.63 |
| Max. Input Power ( KW ) | 23 | 28 |
| Max. Input Current ( A ) | 35 | 43 |
| Compressor | Hitachi Scroll - EVI Technology | |
| Fan Type | High Efficiency Axial Flow Fan | |
| Fan Quantity ( Pcs ) | 2 | 2 |
| Fan Airflow ( m3/h ) | 28000 | 28000 |
| Fan Rated Power ( W ) | 1500 | 1500 |
| Heat exchanger | High Efficient Tube&Shell Type Heat Exchanger | |
| WaterSide Pressure Drop ( Kpa ) | 65 | 65 |
| Inlet/Outlet Pipe Size ( mm ) | DN50 | DN50 |
| Min. Flow ( m3/H ) | >11 | >15 |
| Noise ( dB(A) ) | ≤67 | ≤67 |
| Heating Water Temp. ºC | 20 ~ 60ºC | |
| Cooling Water Temp. ºC | 5 ~ 20 ºC | |
| Operating Ambient Temp. ºC | -35°C~45ºC | |
| Unit Dimension ( mm ) | 1930*980*1890 | 1930*980*1890 |
| Weight ( KG ) | 530kg/550kg | 610kg/700kg |
| Performance Condition - A : Ambient temp. (DB/WB): 7°C/6°C, Water temp. (In/Out): 40°C/ 45°C; | ||
| Performance Condition - B : Ambient temp. (DB/WB): -12°C/-14°C, Water temp. (Out): 41°C | ||
| Performance Condition - C: Ambient temp. (DB/WB): 35°C/24°C, Water temp. (In/Out): 12°C/7°C | ||